LocationDillsburg, York County, Pennsylvania
MarketIndustrial and Environmental
Contract
$45,731
Team Members
- Owner
- Hillandale Farms / Hillandale Feeds
- Prime Contractor
- Control Systems 21
- Trade Subcontractor
- B & R Electrical Contractors, Inc.
Key Accomplishments
- Furnished and installed two active and two spare 4-inch PVC conduits between the transformer vault and the Motor Control Center.
- Installed four 500 MCM copper conductors in each active conduit for the new 800A service.
- BRE furnished and installed a new four-section Motor Control Center rated 800A, 480/277V, 3-phase, 4-wire, NEMA 1.
- Equipped the MCC with an 800A, 3-pole, 65 kAIC main circuit breaker.
- Furnished a comprehensive lineup of full-voltage non-reversing motor starters with integral circuit-breaker protection for facility equipment ranging from fractional horsepower through 30 HP.
- Motor-control equipment included:
- Two 30 HP Size 3 FVNR starters
- Two 20 HP Size 2 FVNR starters
- One 1.5 HP Size 1 FVNR starter
- Furnished MCC feeder breakers including 150A, 90A, 40A, 20A and 200A circuit-breaker provisions.
- BRE provided a 2 HP VFD starter with circuit-breaker protection as part of the motor-control system.
- Incorporated spare MCC sections and spaces into the lineup to accommodate future equipment additions and electrical-system expansion.
Project Description
B & R Electrical Contractors, Inc. served as Trade Subcontractor to Control Systems 21 for construction of a new 800A, 480/277V, 3-phase, 4-wire electrical service serving the Control Building associated with the new Hillandale storage facility.
Extended the secondary electrical service from the pad-mounted transformer, located approximately 25 feet from the Control Building, to the new motor-control equipment.